The
testo 512 PDM meter series includes four different versatile pressure
and velocity meters that can display any of six user-selectable
measurement units.
- Simultaneous display of velocity
and pressure values
- 6 switchable
pressure units: hPa/mbar, mm H2O, mm Hg, psi, in H2O, in
Hg
- 2 switchable velocity
units: m/s, fpm (velocity not available on 5123)
- Adjustable
damping
- ±0.5 % full-scale
value / ± 1 digit
- Integral
density compensation
- Factory
calibration certificate
|
When connected
to a Pitot tube, the testo 512 simultaneously displays pressure and
air velocity.
Applications:
- Simultaneous
measurement of pressure and velocity using a Pitot tube in heating,
ventilation and air conditioning (HVAC) systems
- Monitoring
differential pressure across filters and coils in HVAC systems
-
Measuring positive and negative pressure
in air conditioning ducts
- Measuring
differential pressure for clean room monitoring
|
Technical Data
|
| Sensor | Inductive measurement of membrane displacement |
| Accuracy | 0.5% full-scale value / ±1 digit |
Ranges
(4
different measuring instruments) |
Model 5126: 0-1 in H2O,
0 to 2hPa/mbar
Model 5127: 0-10 in H2O, 0 to 20hPa/mbar
Model 5128: 0-100 in H2O, 0 to 200hPa/mbar
Model 5129: 0 -800 in H2O, 0 to 2000hPa/mbar |
Resolution – Velocity
(with addition of Pitot probe) |
Model 5126: ±0.1 fpm (0-3,350 fpm) or
0.1m/s Model 5127: ±1
fpm (0-10,800 fpm) or 0.1m/s Model
5128: ±1 fpm (0-19,650 fpm) or 1 m/s | | Resolution - Pressure |
Model 5126: ±0.001
in H2O, 0.001 hPa/mbar
Model 5127: ± 0.01 in H2O, 0.01 hPa/mbar
Model 5128: ± 0.1 in H2O, 0.1 hPa/mbar
Model 5129: ± 1.0 in H2O, 1 hPa/mbar |
| Overload |
Model 5126: ±10.0
in H2O (0.0 to 1.0 in H2O)
Model 5127: ±100.0 in H2O (0.0 to 10.0 in H2O)
Model 5128: ±1000.0 in H2O (0.0 to 100.0 in H2O)
Model 5129: ±1600.0 in H2O (0.0 to 800.0 in H2O) |
| Measuring medium | All non-corrosive gases |
| Operating temperature | 32 to 140 °F / 0 to 60 °C |
| Storage temperature | 14 to 158 °F / -10 to 70 °C |
| Battery type | 9V battery | | Battery life | 120 hours | | Auto Off | Approximately 10 min | | Dimensions L x W x H | 7.95 x 2.24 x 1.65 inches / 202 x 57 x 42 mm |
| Weight | 10.58 oz / 300 g | | Warranty | 1 year |
testo
512 Meters |
| Basic Kits include: battery and calibration
certificate | Part
# | | Range:
0 to 1 in H2O (0 to 2 hPa/mbar) | 0560
5126 | | Range:
0 to 10 in H2O (0 to 20 hPa/mbar) |
0560 5127 | | Range:
0 to 100 in H2O (0 to 200 hPa/mbar) |
0560 5128 | | Range:
0 to 800 in H2O (0 to 2000 hPa/mbar) |
0560 5129 |
testo
512 Standard Kits |
512-1
Digital Manometer/Anemometer Kit
0560
5126 512-1 Meter (0 to 1 " H2O)
0635 2145 14" "L" style Pitot tube
0554 0440 16' hose
0516
0182 Carrying Case |
400563
5121 | 512-2
Digital Manometer/Anemometer Kit
0560
5127 512-2 Meter (0 to 10 "H2O)
0635 2145 14" "L" style Pitot tube
0554
0440 16' hose
0516 0182 Carrying
Case |
400563
5122 |
Accessories | Description
| Note | Part no. |
| Pitot
probe, "L" type, 14" long, stainless steel |
Measures velocity flow with 512 meters except for
5128 meters. | 0635 2145 | | Silicone
hose, 16' | |
0554
0440 | | testo
Portable Printer | Wireless
IrDA infrared interface, 1 roll paper, batteries | 0554 0549 |
| Printer Paper | Spare thermal paper (6
rolls) -Legible for up to 10 years | 0554 0568 |
| NIST calibration certificate/Pressure | Differential and positive pressure; 11 measuring
points distributed over the instrument measuring range | 0520 0215 | | ISO calibration certificate/Pressure | 5 points distributed evenly over measuring range
of the object being tested, from 0 to 4000 psi | 0520 0005 | |